Energy Management System for Commercial Kitchen Ventilation System.
- Full capture and containment of heat loads while still reducing energy costs
- 20% reduction in fan speed equates to a 48% reduction in fan energy costs
- Heated make up air savings is linear and reduces gas consumption on low speed
- 100% Airflow Override button with a fully adjustable timer
- Low Maintenance – Monthly temperature probe cleaning only
- Adjustable Set-Points Include: Fan Low Speed, Fan High Speed, Fan Activation Temperature, Fan High Speed Temperature, and Ramping Rate
- Meets the requirements of IMC 507.2.1.1. which require exhaust fans to activate when cooking appliances are energized
- Installed in Exhaust Hood utility cabinet and can be factory wired. Panel can also be wall mounted.
- Fully modulating Digital Temperature Control
|
Commercial Canopy Exhaust Hood with make up air plenum |
|
54” deep x 24” tall 12ft 0" Long Exhaust-Only Wall Canopy Hood with Front Plenum
-Factory install back standoff for 0 clearance rear |
|
- 430 SS Where Exposed |
|
- Fire Cabinet on the Right Side |
|
- FILTER - 16" tall x 16" wide Kleen-Gard Stainless Steel Baffle Filter with Handles and Bottom Hanging Hook, UL Classified |
|
- FILTER - 16" tall x 20" wide Kleen-Gard Stainless Steel Baffle Filter with Handles and Bottom Hanging Hook, UL Classified |
|
- Incandescent Light Fixture, Bulbs By Others |
|
- EXHAUST RISER - Factory installed 10" X 28" |
|
- SUPPLY RISER - 8"x 36" Supply Riser with Volume Dampers |
|
- 1/2 Pint Grease Cup New Style, Flanged Slotted |
|
- Electrical Package Installation in Utility Cabinet by Plant. |
|
Ansual Fire Suppression System |
|
ANSUL-3.0/3.0 Ansul 6 gallon Fire System in Utility Cabinet (includes pre-piped hood(s) with detection, tank(s), release mechanism, microswitches and pull station) |
|
|
|
|
- GAS VALVE - 1-1/4" Mechanical Shutoff Valve (Ansul) (26-55604)
*FINAL HOOK UP, TESTS and PERMITS NOT INCLUDED* |
|
|
|
|
|
|
|
Exhaust Fan |
|
BDU20 Belt Drive Centrifugal Upblast Exhaust Fan with 20.75" wheel
Exhaust Fan handles 3000 CFM @ -1.000" wc. Fan runs at 884 RPM.
Exhaust Motor: 1.500 HP, 3 Phase 208 V, 4.7 FLA, ODP (Open Drip Proof) |
|
|
|
|
- Grease Cup for kitchen-duty centrifugal exhaust fans,
Box Dimensions 15-3/4 L X 5-1/16 W X 3-3/4 H (18 GA.) |
|
|
|
|
- Curb CRB26.5x20E On Fan # 1 |
|
|
|
|
- Hinged Base for Curb. Standard Hinge attached to curb. Used on Fans with wheels 20 inches or smaller. 12 GA Galvanized. |
|
|
|
|
- Vented Base for Curb |
|
|
|
|
|
|
|
Make Up Air Unit |
|
|
|
|
|
|
SA10 Untempered Supply Unit with 10" Blower in Size #1 Housing Supply Fan handles 2400 CFM @ 0.250" wc. Fan runs at 763 RPM. Supply Motor: 1.000 HP, 3 Phase 208 V, 3.3 FLA, ODP (Open Drip Proof) Down Discharge - Air Flow Right -> Left |
|
|
|
| - Sloped Foam Filtered Intake for Size #1 Modular Untempered Supply Unit. 21.813" Wide x 44.375" Long x 23.375" High. Includes 2" Foam EZ Kleen Metal Mesh Filters. |
|
|
|
| - Curb CRB21X12 On Fan # 2 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Energy Management System
EMS11102 Modulating Energy Management System to Control One Exhaust Fan and One Supply Fan. Includes VFDs, Duct Temperature Sensor and Override Control w/Exhaust on in Fire. INVERTER DUTY THREE PHASE MOTORS REQUIRED!
|
|
|  |
| |
|